Specifications * There are different values from standard specifications.
|
Model |
BL-120A |
BL-120W |
BL-180A |
BL-180W |
BL-220A |
BL-220W |
|||
|
Cooling method |
Air -cooled refrigeration |
Water-cooled refrigeration |
Air -cooled refrigeration |
Water-cooled refrigeration |
Air -cooled refrigeration |
Water-cooled refrigeration |
|||
|
Refrigerant |
R134A (HFC) |
||||||||
|
Control method |
PID control |
||||||||
|
Working temperature range |
5 to 3 5 ℃ |
||||||||
|
Circulating Fluid system |
Circulating fluid |
Water |
|||||||
|
Temperature range setting |
5 to 35℃ |
||||||||
|
Cooling capacity at 20℃ (50/60 Hz) |
1200W |
1800W |
2200W |
||||||
|
Temperature stability |
± 0.5 ℃ |
||||||||
|
Pump capacity (50/60 Hz) (MPa) |
15L/min. 3.5kg/cm2 (optional: 20L/min, 5.5kg/cm2 |
||||||||
|
Tank capacity (L) |
5L |
||||||||
|
Port size |
Rc1/2 |
||||||||
|
Facility Water System |
Temperature range (℃) |
|
5 to 35 |
|
5 to 35 |
|
5 to 35 |
||
|
Pressure range (MPa) |
|
0.3 to 0.4 |
|
0.3 to 0.4 |
|
0.3 to 0.4 |
|||
|
Required flow rate (50/60 Hz) (L/min) |
|
8 |
|
8 |
|
8 |
|||
|
Inlet-outlet pressure differential of facility water (MPa) |
|
0.3 or more |
|
0.3 or more |
|
0.3 or more |
|||
|
Port size |
Rc1/2 |
||||||||
|
Electrical System
|
Power supply |
110V / 220V AC (50/60 Hz) Allowable voltage range ±10% |
|||||||
|
Circuit protector |
20A |
||||||||
|
Applicable earth leakage breaker capacity |
30A |
||||||||
|
Rated power consumption (50/60 Hz) (kVA) |
10A/5A |
8A |
8A |
||||||
|
Weight (kg) |
69Kg |
93Kg |
93Kg |
||||||
|
Overall Dimension (mm) |
600 x 430 x 660 |
600 x 430 x 950 |
600 x 430 x 950 |
||||||